Water temperature to process adjustable from 50° to 80°F
3-10 GPM flow required to process at 125-225 PSI
Water components constructed of nonferrous materials
Deionization/Deoxygenation system optional
HE-1010
PlasmaGun® WATER CHILLER
FOR THE 80 KW PLASMAGUN SYSTEM
SPECIFICATIONS
Model:
HE-1010
Voltage:
460V/3/60
Capacity:
10.0 tons
MCA:
36 amps
(65°F lwt, 95°F ambient)
Operating Range:
50°F – 80°F
Refrigerant:
HCFC-22
Shipping Weight:
950 lbs
Pump:
7½ HP
Dimensions:
74"L x 34"W x 55"H
Flow to Process:
3-10 GPM
Process Connections:
1½" FNPT
Pressure:
125-225 PSI
Condenser Air Flow:
8,100 CFM
MECHANICAL FEATURES
Generously sized condenser for industrial environments (up to 115°F ambient temperatures)
Twin top discharge fans and cleanable inlet air filter
Energy efficient and reliable scroll compressor
Electronic hot gas bypass for capacity control
Brazed plate evaporator provides higher heat transfer coefficients due to reduced fouling
Refrigerant TXV, filter/drier, and sight glass
Freezestat safety switch with solid state sensor
Encapsulated high and low refrigerant pressure safeties
Nonferrous water circuit construction
Insulated polyethylene reservoir with sight glass and removable cover
Stainless steel process pump with pressure gauge
Fail safe flow switch interlocked with compressor
Flow switch and Flow meter in process return line
Y-strainer on supply and return lines to protect evaporator from contamination
Pressure regulated bypass valve to set process flow and pressure
Compressed air purge
Factory tested under full load conditions prior to shipment
ELECTRICAL FEATURES
NEMA-12 electrical enclosure with single point electrical connection
Control transformer to provide 115V/1/60 control voltage
Dual LED digital displays of actual and set point temperatures
PID control algorithm
Anti-cycle timer to prevent short-cycling of compressor
Diagnostic lights (No Flow, High Refrigerant Pressure, Low Refrigerant Pressure, Freezestat, Under Set Point, Over Set Point, Pump On, Compressor On, Partial Load, High Water Temperature, Probe Fault)
24VDC signal for remote on/off capability
Contact closure for system normal (contacts open upon chiller fault)
Switches with indicating lights (Power, Start, Stop, Alarm Reset)