PRODUCT DATA SHEET Model No. HE-1010 Chiller
|
|
KEY FEATURES
- 10 tons (120,000 BTUH) of heat removal is require
- Water temperature to process adjustable from 50° to 80°F
- 3-10 GPM flow required to process at 125-225 PSI
- Water components constructed of nonferrous materials
- Deionization/Deoxygenation system optional
|
HE-1010
PlasmaGun® WATER CHILLER
FOR THE 80 KW PLASMAGUN SYSTEM
|
SPECIFICATIONS |
|
|
Model:
|
HE-1010
|
Voltage:
|
460V/3/60
|
|
Capacity:
|
10.0 tons
|
MCA:
|
36 amps
|
|
(65°F lwt, 95°F ambient)
|
|
Operating Range:
|
50°F – 80°F
|
|
Refrigerant:
|
HCFC-22
|
Shipping Weight:
|
950 lbs
|
|
Pump:
|
7½ HP
|
Dimensions:
|
74"L x 34"W x 55"H
|
|
Flow to Process:
|
3-10 GPM
|
Process Connections:
|
1½" FNPT
|
|
Pressure:
|
125-225 PSI
|
Condenser Air Flow:
|
8,100 CFM
|
|
MECHANICAL FEATURES |
- Generously sized condenser for industrial environments (up to 115°F ambient temperatures)
- Twin top discharge fans and cleanable inlet air filter
- Energy efficient and reliable scroll compressor
- Electronic hot gas bypass for capacity control
- Brazed plate evaporator provides higher heat transfer coefficients due to reduced fouling
- Refrigerant TXV, filter/drier, and sight glass
- Freezestat safety switch with solid state sensor
- Encapsulated high and low refrigerant pressure safeties
- Nonferrous water circuit construction
- Insulated polyethylene reservoir with sight glass and removable cover
- Stainless steel process pump with pressure gauge
- Fail safe flow switch interlocked with compressor
- Flow switch and Flow meter in process return line
- Y-strainer on supply and return lines to protect evaporator from contamination
- Pressure regulated bypass valve to set process flow and pressure
- Compressed air purge
- Factory tested under full load conditions prior to shipment
|
|
|
ELECTRICAL FEATURES |
- NEMA-12 electrical enclosure with single point electrical connection
- Control transformer to provide 115V/1/60 control voltage
- Dual LED digital displays of actual and set point temperatures
- PID control algorithm
- Anti-cycle timer to prevent short-cycling of compressor
- Diagnostic lights (No Flow, High Refrigerant Pressure, Low Refrigerant Pressure, Freezestat, Under Set Point, Over Set Point, Pump On, Compressor On, Partial Load, High Water Temperature, Probe Fault)
- 24VDC signal for remote on/off capability
- Contact closure for system normal (contacts open upon chiller fault)
- Switches with indicating lights (Power, Start, Stop, Alarm Reset)
|
|
|
|
 |
|
|
|
|
|
|
|